Battery Storage

The battery should be stored under the following conditions.
(1) Low humidity
(2) 5 to 122℉(-15 to 50℃)
(3) Clean, and avoid direct sunlight.

After long term storage, all batteries deliver less than rated capacity on first cycle. In cyclic
application, full capacity may be obtained through several charge/discharge cycles,
typically 2-3 cycles.

When batteries are placed in extended storage, it is recommended that they receive a refresh
charge at recommended intervals as following;
Refresh charging method:
3 to 5 hours of constant current 0.1C Amps or 12 to 16 hours at constant voltage of 2.45V/cell
Storage Ambient:    Recommended Interval

Storage Ambient:

Recommended Interval

Below 20 (68):

12 months

20 to 30(68 to 86):

6 moths

30 to 40(86 to 104):

3 moths


Figure 7 shows the time for the capacity to decrease to 50% of nominal capacity at each
temperature during storage. If the storage temperature is known, the graph may be used
for finding the most useful recommended refresh charge intervals.